低压配电系统用电涌保护器符合性认定检测细则.doc
13页通 信 局 ( 站 ) 低 压 配 电 系 统 用 电 涌保 护 器 检 验 实 施 细 则I目 录1 编制依据及适用范围 ···························································································· 12 引用标准 ·················································································································· 13 检验项目及技术要求····························································································· 13.1 检验项目及技术要求····················································································· 13.2 对各种类型 SPD 检测项目········································································· 74 检验方法·················································································································· 95 抽样 ························································································································· 95.1 抽样基数········································································································· 95.2 样品数量········································································································· 96 质量判定 ················································································································· 9II6.1 通信局(站)低压配电系统用电涌保护器监督总体的检验项目和质量判定 ····················································································································· 9 6.2 判定准则·········································································································· 91通信局(站)低压配电系统用电涌保护器检验实施细则1 编制依据及适用范围本实施细则依据 YD/T1235.1-2002《通信局(站)低压配电系统用电涌保护器技术要求》编制。
本细则适用于通信局(站)低压配电系统用电涌保护器的质量检验2 引用标准GB/T4942-1993 低压电器外壳防护等级(eqv IEC60947:1988)YD/T1235.2-2002 通信局(站)低压配电系统用电涌保护器测试方法3 检验项目及技术要求3.1 检验项目及技术要求(见表 1 至表 10)表 1 检验项目及技术要求序号 项目名称 技术要求1 外观质量a)电涌保护器表面应平整、光洁、无划伤、无裂痕及变形,紧固件应牢固,颜色应均匀无明显差异b)标志应完整清晰、耐久可靠,内容完全,且铭牌不应出现移动和任何翘曲现象2 保护模式交流 SPD 必须具备 N-PE、L-PE 或 L-N-PE 的保护模式;直流 SPD 必须具备 V+-V-的保护模式交流 SPD 宜具备 L-N 的保护模式;直流 SPD 宜具备 V+-PE 或 V--PE 的保护模式3 分离装置 SPD 在故障或失效时,应有与电源系统永久断开的分离装置4 告警功能SPD正常或故障时,应有能正确表示其状态的标志或指示灯SPD 宜具备远程集中监测或集中告警的接口5接线端子连接导体的能力SPD 的接线端子除应符合 GB17464 的要求外,其连接导线的能力还应符合表 2 或表 3 的要求。
2序号 项目名称 技术要求6 最大持续运 行电压在70±3℃的试验环境下,施加规定的U c持续48h,SPD应满足下列要求:a) 试验过程中,SPD应能稳定地正常工作、没有可见可闻的损坏;b) 试验前后的限制电压和点火电压应小于U P,且限制电压的变化率不应大于±5%;c) 试验过程中,SPD 的分离装置不应动作7 电压保护水 平 SPD 的电压保护水平 UP 应符合制造商所规定的数值8 等级限制电 压 施加表 4 规定的等级测试电流 IB 时,限压特性的 SPD的等级限制电压 UB 应符合表 4 的要求9 动作负载试 验在最大持续运行电压U c下, SPD应能耐受规定波形、幅值和次数的冲击电流而不发生实质性损坏SPD的雷击动作负载试验通过的判据如下:a) 在预备性试验和动作负载试验期间的每次冲击后,SPD都应能满足热平衡的要求;b)SPD应能自行遮断试验中产生的任何续流;c) 试验中SPD应不出现击穿、闪络或机械损伤等现象;d)试验前后的限制电压和点火电压均应小于U P;e)试验中SPD的告警或分离装置不应动作10 电气间隙和 爬电距离 电气间隙和爬电距离应符合表 5 的要求11 外壳防护等 级SPD的外壳防护等级(IP代码)应符合GB4942.2中规定的IP2LX。
12 保护接地a)SPD 在按正常使用条件安装和连接时,其非带电的易触及的金属部件(用于固定基座、罩盖、铆钉、铭牌等以及与带电部件绝缘的小螺钉除外)应连接成一个整体后与保护接地端子可靠连接;b)保护接地端子螺钉的尺寸应不小于 M4;c)保护接地应采用符合国标的标记加以识别,如:字母标记 PE,图形符号〨等3序号 项目名称 技术要求13着火危险性(灼热丝试验)SPD的绝缘部件必须有足够的阻燃能力绝缘部件在进行表6规定的灼热丝试验时,试品在下列情况可看作通过了试验:——没有可见的火焰或持续火光;——灼热丝移开后,试品上的火焰或火光在 30s 内自行熄灭,并且不应点燃试验用的铺底层中的薄绵纸(绢纸) 、或烧焦松木板14 暂时过电压失效安全性安装在L-PE或N-PE之间的SPD,在施加表7规定的异常的暂时过电压UT条件下,SPD故障时应具有安全的失效模式,试验期间不能点燃薄绵纸或粗绵布15 暂时过电压 耐受特性安装在 L-PE 或 L-N 之间的 SPD 应能耐受表 8 规定的暂态过电压 UT,并满足如下技术要求:a) UT 断开后,SPD 在 Uc 下应能达到热平衡;(注:如果在施加 Uc 的最后 15min 内,SPD 的功耗或温度或流过 SPD 的阻性电流分量能稳定地降低,则认为 SPD 达到热平衡。
b) 试验后 SPD 的限制电压和点火电压均应小于 UP;c) SPD 的辅助电路,如状态指示灯应能正常地工作;注:电涌保护电路以外的其它电路称为辅助电路d) SPD 没有出现任何损坏的迹象16 热稳定性按表9规定的每一试验电流等级进行的热稳定性试验时,SPD应满足如下要求:a) SPD持续通过每一档试验电流等级时,都应能达到热平衡或使其分离装置动作;注:当电流持续通过SPD时,10min内其温度的增加值小于2℃,则认为达到热平衡b)在试验期间,SPD的表面温度应始终低于120℃;分离装置动作后在5min内,SPD的表面温度应低于80℃c)如果 SPD 的分离装置动作,则对应 SPD 施加 2Uc的工频电压,持续 1min,此时应无超过 0.5mAr.m.s 的电流流过 SPD17 电压降a) 二端口交流 SPD 的 L-N 之间通过电阻性的额定负载电流 IR 时,在稳定条件下,同时测量的输入端口与输出端口之间的电压降应不大于 2%b)二端口直流SPD的V +-V-之间通过电阻性的额定负载电流I R时,在稳定条件下,同时测量的输入端口与输出端口之间的电压降,应不大于0.5%4序号 项目名称 技术要求18 负载侧电涌 耐受能力 二端口 SPD 的负载侧应能承受制造商规定的电涌电流的冲击。
19负载侧短路耐受能力在负载短路的条件下,二端口SPD应能承载制造商规定的短路电流预期短路电流和功率因数应根据表10给出试验结果的合格判据如下:a) 试验过程中,短路电流应在 5s 中断开,薄绵纸或粗绵布应不着火此外,不应有爆炸或对人身或设施的其它危害发生b) 如果分离装置动作,则对应 SPD 施加 2Uc 的工频电压,持续 1min,此时应无超过 0.5mAr.m.s 的电流流过SPD注:17,18,19 项不适用一端口SPD表2 一端口SPD接线端子允许连接铜导线的标称截面积SPD 类型 能被夹紧的导线标称截面尺寸 mm2交流 SPDT 型H 型M 型L 型25~5016~3510~254~16直流 SPD H 型L 型 4~162.5~65表3 二端口SPD接线端子允许连接铜导线的标称截面积额定负载电流 IRA能被夹紧的导线标称截面尺寸mm2IR≤1313 2 二端口 SPD 接线端子连接导线的能力除应符合本表的要求外,还应根据其标称放电电流的大小,同时符合表 3 的要求表 4 限压特性的 SPD 的等级限制电压 UB交流 SPD 的 UB 上限值(V ) 直流 SPD 的 UB 上限值(V)M 型最大持续运行电压Uc T 型( IB=60kA )H 型( IB=40kA ) ( IB=25kA) ( IB=15kA )L 型( IB=5kA )H 型( IB=5kA )L 型( IB=2kA )45V — — — — — 425 25052V — — — — — 450 27575V — — — — — 500 32585V — — — — — 550 350275V 2600 2100 1600 1250 950 — —320V 2850 2300 1700 1450 1150 — —385V 3200 2600 2000 1800 1400 — —420V 3450 2800 2200 1900 1600 — —460V 3700 3000 2500 2100 1750 — —510V 3950 3200 2700 2300 1900 — —600V 4400 3600 3100 2700 2300 — —6表 5 电气间隙和爬电距离检 查 部 位1) 接线端子不同相的带电导体之间。 2) 接线端子各相与:接地端子、零线端子之间;固定 SPD 的金属螺钉、外壳、机箱、面盖或其它金属工件之间 SPD 的 Uc <10。