南瑞发变定值计算.doc
50页RCS-985 发电机变压器组保护装置 NARI-RELAYS RCS-985 发电机变压器成套保护装置300MW 机组保护整定计算书1300MW 机组发电机变压器保护定值计算1 原始资料 ................................................................................................................................21.1 发电机变压器参数 ..................................................................................................21.2 整定计算相关资料 ..................................................................................................22 短路电流计算 ........................................................................................................................33 发电机变压器组保护配置方案 ............................................................................................63.1 发电机变压器主接线方式 ........................................................................................63.2 发电机变压器保护配置 ............................................................................................74 整定计算 ................................................................................................................................84.1 发电机差动保护 ........................................................................................................84.2 主变压器差动保护 ....................................................................................................94.3 发电机纵向零序电压匝间保护 ..............................................................................124.4 定子绕组接地保护 ..................................................................................................124.5 转子接地保护 ..........................................................................................................134.6 定子绕组对称过负荷保护(反时限) ......................................................................144.7 励磁绕组过负荷保护 ..............................................................................................144.8 转子表层负序过负荷保护(发电机负序过负荷保护) ..........................................154.9 发电机失磁保护 ......................................................................................................164.10 发电机失步保护 ....................................................................................................194.11 发电机过励磁保护 ................................................................................................214.12 发电机频率异常运行保护 ....................................................................................214.13 发电机逆功率保护 ................................................................................................224.14 发电机定子过电压保护 ........................................................................................234.15 启停机保护 ............................................................................................................234.16 厂变压器差动保护 ................................................................................................234.17 发变组差动保护 ....................................................................................................254.18 主变压器零序过流过压保护 ................................................................................274.19 主变压器过负荷保护 ............................................................................................274.20 高压厂用变压器高压侧复合电压过流保护 ........................................................274.21 高压厂用变压器 A 分支零序过流保护 ................................................................284.22 高压厂用变压器 B 分支零序过流保护 ................................................................294.23 通风启动 ................................................................................................................294.24 非电量保护 ............................................................................................................304.24 跳闸方式 ................................................................................................................305 RCS-985A 装置定值单 .....................................................................................................315.1 装置参数 ..................................................................................................................315.2 系统定值 ..................................................................................................................315.3 保护定值 ..................................................................................................................345.3 计算定值 ..................................................................................................................4721 原始资料1.1 发电机变压器参数(1)发电机 QFSN-300-20B(水.氢.氢)Pn=300MW;COSФ=0.85;U n=20KV;I n=10189A; Xd〞=14.58%(饱和值);Xd〞=16.94%( 非饱和值) ;Xd′=21.25%(饱和值);Xd′=24.15%( 非饱和值) ;Xd=184.4%(饱和值);Xd=184.4%( 非饱和值) 。
2)主变压器 SFP10-370000/242Sn=370000KVA;242±2×2.5%/20KV,Yn,d11;Ud=14%3)厂用变压器 SFF-50000/20Sn=50000/31500-31500KVA;20±2×2.5%/6.3-6.3;Ud1-2′=Ud1-2〞=21%;D,yn1-yn1(4)励磁变压器Sn=3235KVA;20/0.94KV;d,y111.2 整定计算相关资料《大型发电机变压器继电保护整定计算导则》《电力工程电气设计手册》《RCS-985A 型发电机变压器成套装置技术使用说明书》《RCS-974A 型发电机变压器成套装置技术使用说明书》技术数据取自发电机.变压器产品说明书32 短路电流计算短路计算如图 1,电网对本电厂系统电抗,为一点等值,如下:a. 等值方式:不含本电厂 220KV#1 机变组,b. 正常方式: 2854.0Xc. 检修方式: 39d. 以 10。