110kV电力变压器参数表.doc
2页型号额定容量(kVA)额定电压联结组标号损耗(kW)空载电流(%)短路阻抗(%)高压(kV)低压(kV)空载负载SF11-6300/1106300110±2X6.37.434.20.77SF11-8000/11080002.50%6.69.642.80.77SF11-10000/1101000010.510.650.40.72SF11-12500/11012500121±2X1112.559.90.72SF11-16000/110160002.50%1573.20.67SF11-20000/1102000017.688.40.6710.5SF11-25000/1102500020.8104.50.62SF11-31500/11031500YNd1124.6126.40.6SF11-40000/1104000029.4148.20.56SF11-50000/1105000035.2184.30.52SF11-63000/1106300041.6222.30.48SF11-75000/1107500013.847.2264.10.42SF11-90000/1109000015.7554.43040.38SF11-120000/1101200001867.8377.20.3412〜14SF11-150000/1101500002080.2448.40.3SF11-180000/11018000090505.40.25注1:-5%分接位置为最大电流分接。
注2:对于升压变压器,宜采用无分接结构如运行有要求,可设置分接头重量(kg)外形尺寸(mm)轨距(mm)器身重油重总重长宽高98904880189004210325040501435X1435102905730224004550340042951435X1435136506820261004850373548301435X1435146607835280004900381016001435X1435182508670335004960416550602000X1435202409080396005960453548202000X1435218009990413506090474050102000X14352788511400451506565447053652000X14353366014200552006765486054102000X14353459015890598006810485061002000X14353990017900678006900489061502000X14354620018700765006970498061902000X14355370020100893007200506063002000X14355380020400899007300516064002000X14355390020800903007400526065002000X14355400021200906007500536066002000X1435。