    • CHAPTER 19DATA PROCESSING AND TELECOMMUNICATION FACILITIES第19章数据处理和电信设施Design CriteriaHVAC Load considerationsHVAC Systems and ComponentsAir Distribution Ancillary spaces Other Systems and considerations19.1 设计标准19.2 空调负荷注意事项19.3 空调系统和组件19.4 气流组织19.5 辅助空间19.6 其它系统和注意事项DATACOM (data processingandtelecommunications)facilities are predominantly occupied by computers, networking equipment, electronic equipment, and peripherals. The most definingHVAC characteristic of data and communications equipment centers is the potential for exceptionally high sensible heat loads (oftenorders of magnitude greater than a typical officebuilding). In addition, the equipment installed in these facilities typically:数据通信(数据处理和电信)设施主要由计算机、网络设备、电子设备和其它辅助设备组成。

      数据和通讯设备中心空调最主要的特征是,需要应对极高的显热冷负荷(要比普通的商业办公楼负荷大得多)另外,空调系统要具有以下这些功能:.Serves mission-critical applications (i.e., continuous operation).Has special environmental requirements (temperature, humidity, and cleanliness).Has the potential for disruptive overheating and equipment failurecaused by loss of cooling·满足特定的应用(例如:持续运行);·具备特殊环境要求(温度、湿度和洁净度);·在突发性过热和由于设备损坏不能持续制冷的情况下,系统能继续冷却电子设备 Design of any datacom facility should also address the fact thatmost datacom equipment will be replaced multiple times with morecurrent technology during the life of the facility. As described inDatacom Equipment Power Trends and Cooling applications(ASHRAE 2005a), typical datacom equipment product cycles are 1 to 5 years, whereas facilities and infrastructure HAVC life cycles of10 to 25 years. Replacement equipment has historically requiredmore demanding power and cooling requirements.任何数据通信设施的设计时,都要面对这样一个事实:在通信设施的使用寿命期间,随着技术的发展,大量现有的通信设备将会被将来的新设备更换掉。

      在数据通信设备电源的发展过程和冷却应用中(ASHRAE 2005a),典型的数据通讯设备产品寿命为1至5年,而空调设施和基础设施的寿命为10年至25年新设备对电功和制冷量要求的会更大 Understanding these critical parameters is essential to datacomfacility design.了解这些关键因素对数据通信设施的设计是必不可少的The preparation of this chapter is assigned to TE 9.9, Mission-criticalFacilities, Technology Spaces, and Electronic Equipment.由ASHRAE中负责“重要设施、工艺房间与电子设备”的技术委员会TC9.9编著Design Criteria19.1 设计标准Types of datacom(ASHRAE 2005a)equipment that require airconditioning to maintain proper environmental conditions include数据通信中心(ASHRAE 2005a)的空调系统的工作环境中,包含的数据通信设备类别有:·Computer servers (2U and greater)·Computer servers (1U, blade, and custom)·Communication (High-density)·Communication (Extreme-density)·tape storage·Storage servers·Workstations(standalone)·Other rack- and cabinet-mounted equipment·服务器(2台或更多)·服务器(1台, black, and custom)·通讯(高密度)·通讯(超高密度)·磁带存储器·存储服务器·工作站(独立)·其它机架和机柜安装设备Personnel also occupy datacom facilities, but their occupancy istypically transient and environmental conditions (e.g., temperature,noise) are more typically dictated by equipment needs. However,human occupancy in smaller datacom facilities may influence theventilation air quantity. A data center is a building or portion of abuilding whose primary function is to house a computer room andits support areas; data centers typically contain high-end servers andstorage products with mission-critical functions. Personnel alsooccupy datacom facilities, but their occupancy is typically transientand environmental conditions are usually more dictated by equipment needs, thereby making it more of a process cooling applicationrather than comfort cooling. However, human occupancy in smallerdatacom facilities may influence ventilation air requirements.工作人员也占用数据通信中心,但其通常是暂时的,所以机房环境条件(如温度,噪音)常由设备的需求决定。

      虽然工作人员占用的数据通信机房较小,但通风量也会受影响数据中心可能一个建筑物或建筑物的一部分,其主要功能是容纳一个计算机房和其他附属设施;数据中心通常包含高端服务器和具有重要功能的存储设备工作人员也占用数据通信中心,但其通常是暂时的,所以机房环境条件(如温度,噪音)常由设备的需求决定,因此空调系统更多的是冷却功能而不是舒适功能虽然工作人员占用的数据通信机房较小,但对通风设计也会有要求Overview19.1.1 概述Environmental requirements ofdatacom equipment vary depending on the type of equipment and/or manufacturer. However, a consortium of server manufacturers has agreed on a set of fourstandardized conditions (Classes 1 to 4), listed in Thermal Guidelines for Data Processing Environments(ASHRAE 2008). A fifthclassification, the Network Equipment-Building Systems (NEBS)class, is typically used intelecommunications.不同类型的设备或制造商,他们的数据通信设备对环境的要求都有所不同。

      然而,服务器制造厂家们达成了四个标准原则,此四条标准原则列于数据中心冷却指南(Thermal Guidelines for Data Processing Environments ASHRAE 2008)第五个分类,网络设备构建系统(NEBS)类,通常用于通信·Class 1: typicallya datacom facility with tightly controlled environmental parameters (dew point, temperature, and relativehumidity) and mission-critical operations;types of products typically designed for these environments areenterprise servers andstorage products.·第一类:通常数据通信设施有严格控制环境参数(露点,温度和相对湿度)和重要操作;通信设备服务器和存储设备一般按照此条规定的环境参数设计·Class 2: typically a datacom space or office or lab environmentwith some control of environmental parameters (dew point, temperature, and relative humidity); types of products typically designedfor this environment are small servers, storage products,personal computers, and workstations.·第二类:通常。