WFH-31A-01微机发电机保护装置说明书.doc
17页WFH-31A/01微机发电机保护装置使用说明书1 前言WFH-31A/01微机发电机保护装置,主要适用于中小型发电厂或水电站机组,数字式多CPU并行运行设计,实现对发电机的差动、后备、失磁、接地等功能2 整定参数总汇(见表1)表1类别序号整定名称整定范围级差差动保护参数整组投退1整组投退√∕×差速断1投退√∕×2动作电流0.40A~99.99A0.01A差 动3投退√∕×4CT断线投退√∕×5CT断线闭锁差动√∕×6突变量启动投退√∕×7动作电流0.40A~99.99A0.01A8拐点电流10.40A~99.99A0.01A9拐点电流20.40A~99.99A0.01A10比例制动系数10.00~99.990.0111比例制动系数20.00~99.990.0112平衡系数0.00~99.990.0113突变量启动定值0.40A~99.99A0.01A14有流定值0.40A~99.99A0.01A公共参数1差流越限投退√∕×2电流定值0.40A~99.99A0.01A3返回系数0.00~9.990.014动作延时0.01s~99.99s0.01s5跳闸保持0.01s~99.99s0.01s6电流Ie0.40A~99.99A0.01A跳闸选项1差速断跳1#DL~8#DL√∕×2差动跳1#DL~8#DL√∕×后备保护参数整组投退1整组投退√∕×复闭过流1Ⅰ段投退√∕×2Ⅰ段经低电压√∕×3Ⅰ段经负序电压√∕×4 低压保持√∕×5Ⅱ段投退√∕×6Ⅱ段经低电压√∕×7Ⅱ段经负序电压√∕×8 低压保持√∕×9Ⅲ段投退√∕×10Ⅲ段经低电压√∕×11Ⅲ段经负序电压√∕×12 低压保持√∕×表1(续)类别序号整定名称整定范围级差后备保护参数复闭过流12Ⅰ段定值0.40A~99.99A0.01A13返回系数0.00~9.990.0114动作延时0.01s~99.99s0.01s15Ⅱ段定值0.40A~99.99A0.01A16返回系数0.00~9.990.0117动作延时0.01s~99.99s0.01s18Ⅲ段定值0.40A~99.99A0.01A19返回系数0.00~9.990.0120动作延时0.01s~99.99s0.01s21负序电压定值0.40V~99.99V0.01V22返回系数0.00~9.990.0123低电压定值0.40V~99.99V0.01V24返回系数0.00~9.990.01过电压1投退√∕×2电压定值0.40V~199.99V0.01V3返回系数0.00~9.990.014动作延时0.01s~99.99s0.01s过负荷1投退√∕×2电流定值0.40A~99.99A0.01A3返回系数0.00~9.990.014动作延时0.01s~99.99s0.01s公共参数1跳闸保持0.01s~99.99s0.01s2PT断线投退√∕×3PT断线闭锁复合电压√∕×跳闸选项2复闭过流Ⅰ段跳1#DL~8#DL√∕×3复闭过流Ⅱ段跳1#DL~8#DL√∕×4复闭过流Ⅲ段跳1#DL~8#DL√∕×5过电压跳1#DL~8#DL√∕×6过负荷跳1#DL~8#DL√∕×接地保护参数整组投退1整组投退√∕×定子判据1投退√∕×2U2闭失步投退√∕×3方向元件√∕×4阻抗元件√∕×5XA-999.99W~999.99W0.01W6XB-999.99W~999.99W0.01W7d0°~359°1°8动作延时0.01s~99.99s0.01s9电压U20.40V~99.99V0.01V10有流定值0.40A~99.99A0.01A11方向元件角度0°~90°1°表1(续)类别序号整定名称整定范围级差接地保护参数转子判据1投退√∕×2转子电压定值0.40V~299V0.01V3返回系数0.00~9.990.014动作延时0.01s~99.99s0.01s低压判据1投退√∕×2低电压定值0.40V~99.99V0.01V3返回系数0.00~9.990.014动作延时0.01s~99.99s0.01s转子接地1投退√∕×2一点接地投退√∕×3二点接地投退√∕×4接地电阻定值0.01KW~999.99KW0.01KW5一点接地返回系数0.00~9.990.016一点接地动作延时0.01s~99.99s0.01s7二点接地动作延时0.01s~99.99s0.01s8二点Δa定值0.00~1.000.019阈值电压0.10V~10.00V0.01V10启动电压0.40V~99.99V0.01V定子接地1基波判据√∕×2三次谐波判据√∕×3判据1√∕×4判据2√∕×5电压定值0.40V~199.99V0.01V6返回系数0.00~9.990.017动作延时0.01s~99.99s0.01s8闭锁电压定值0.40V~199.99V0.01V9Kpr±0.01~±99.990.0110Kpx±0.01~±99.990.0111制动系数Kres0.00~9.990.0112返回系数0.00~9.990.0113动作延时0.01s~99.99s0.01s14动作阈值0.40V~99.99V0.01V零序电流1Ⅰ段投退√∕×2Ⅱ段投退√∕×3Ⅰ段方向投退√∕×4Ⅱ段方向投退√∕×5Ⅰ段零压闭锁√∕×6Ⅱ段零压闭锁√∕×7Ⅰ段定值0.40A~100.00A0.01A8Ⅰ段返回系数0.00~9.990.019Ⅰ段动作延时0.01s~99.99s0.01s表1(完)类别序号整定名称整定范围级差接地保护参数零序电流10Ⅱ段定值0.40A~100.00A0.01A11Ⅱ段返回系数0.00~9.990.0112Ⅱ段动作延时0.01s~99.99s0.01s13零压闭锁定值0.40V~199.99V0.01V14最大灵敏角0°~359°1°公共参数1跳闸保持0.01s~99.99s0.01s2判PT断线√∕×3PT断线闭锁√∕×跳闸选项1一点接地跳1#DL~8#DL√∕×2二点接地跳1#DL~8#DL√∕×3零序过压跳1#DL~8#DL√∕×4零流Ⅰ段跳1#DL~8#DL√∕×5零流Ⅱ段跳1#DL~8#DL√∕×6定子判据跳1#DL~8#DL√∕×7转子判据跳1#DL~8#DL√∕×8低电压判据跳1#DL~8#DL√∕×3 面板操作指南3.1 主菜单WFH-31A/01微机发电机保护装置键盘含义如下(菜单显示信息用斜体字表示,按键用方框阴影表示):启动 进入主菜单↑、↓ 上下移动亮条或修改数值→、← 左右移动亮条确认 确认操作退出 返回到上一级菜单,直至退出主菜单复位 使装置重新启动复归 手动复归灯光及信号具体操作如下:按启动键进入主菜单,液晶显示菜单结构如下:差动保护后备保护接地保护按↑、↓键移动亮条,选择〖差动保护〗、〖后备保护〗、〖接地保护〗选项,按确认键确认。
差动保护、后备保护和接地保护保护的主菜单结构相同,显示如下:模块号设置保护定值设置变比设置系统参数相差显示监测显示报文显示开出传动修改密码滚屏显示,按↑、↓键移动亮条,选择菜单项,然后按确认键确认显示屏的右下角有一闪动的光标,指示上下方是否还有菜单信息菜单项如需输入密码时,要输入除复位键以外的其他键组成的六位密码,如果输入密码错误时提示“密码错误请退出”,输入密码正确时,进入相应菜单项的子菜单输入密码时“按键”与“数字”的对应关系为:启动 键对应数字1 确认 键对应数字5↑ 键对应数字2 → 键对应数字6退出 键对应数字3 ↓ 键对应数字8← 键对应数字4 复归 键对应数字93.2 模块号设置在主菜单上选择〖模块号设置〗选项(将亮条移至〖模块号设置〗选项,按确认键),输入密码后即可进入〖模块号设置〗子菜单,显示如下:模块号 01首先按确认键,待字符闪动以后按→、←键选择要修改个位还是十位,按↑、↓键修改数值,设置结束后按确认键确认在设置过程中如想取消设置,按退出键即可模块号设置范围为1~60。
注: 用户不可随意更改装置的模块号3.3 保护定值设置在主菜单上选择〖保护定值设置〗选项,输入密码后即可进入〖保护定值设置〗子菜单,显示如下:(以差动保护为例)整组投退差速断参数差动参数差流越限参数跳闸选项后备保护的〖保护定值设置〗选项包括〖整组投退〗、〖复闭过流参数〗、〖过电压参数〗、〖过负荷参数〗及〖跳闸选项〗;接地保护保护的〖保护定值设置〗选项包括〖整组投退〗、〖低励失磁参数〗、〖转子接地参数〗、〖定子接地参数〗及〖跳闸选项〗,设置方法与差动保护相同3.3.1 整组投退选择〖整组投退〗选项,显示如下:整组投入 ×整组退出 。